Low Voltage Cables/ Current Ratings And Voltage Drop List/Rating factors for Variation in Thermal Resistivity of Soil for Two Single-Core Cables in Ducts


Rating factors for Variation in Thermal Resistivity of Soil for Two Single-Core Cables in Ducts

Rating Factors for Variation in Thermal Resistivity of Soil for Two Single-Core Cables in Ducts:

Nominal Area of Conductor mm²

Thermal Resistivity of Soil in K.m/W
  0.7  0.8 0.9  1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0
 50 1.08 1.06 1.04 1.03  1.00  0.96 0.90 0.85 0.81 0.77 0.74
70 1.08 1.06 1.05 1.03 1.00  0.96  0.90 0.84 0.80 0.76 0.73
95  1.08 1.07 1.05 1.03  1.00  0.95 0.89 0.84 0.80 0.75 0.72
120 1.09 1.07 1.05 1.03 1.00 0.95 0.89 0.83 0.79 0.75 0.71
150 1.09 1.07 1.05 1.03  1.00  0.95 0.88 0.83 0.79 0.74 0.71
185 1.09 1.07 1.05 1.03  1.00  0.95 0.88 0.83 0.78 0.74 0.70
240 1.10 1.08 1.05 1.04  1.00  0.95 0.88 0.82 0.78 0.73 0.70
300 1.10 1.08 1.06 1.04  1.00  0.95 0.87 0.82 0.77 0.72 0.69
400 1.11 1.08 1.06 1.04  1.00  0.94 0.87 0.82 0.77 0.72 0.68
500 1.12 1.08 1.06  1.04  1.00  0.94 0.87 0.81 0.76 0.71 0.68
630 1.12 1.09 1.06 1.04  1.00  0.94 0.87 0.81 0.76 0.71 0.67
800 1.13 1.10 1.07 1.04  1.00  0.94 0.86 0.80 0.75 0.71 0.67
1000 1.13 1.10 1.07 1.04  1.00  0.94 0.86 0.80 0.75 0.70 0.66