Rating Factors for Variation in Thermal Resistivity of Soil for Two Single-Core Cables in Ducts:
Nominal Area of Conductor mm²
|
Thermal Resistivity of Soil in K.m/W |
|
0.7 |
0.8 |
0.9 |
1.0 |
1.2 |
1.5 |
2.0 |
2.5 |
3.0 |
3.5 |
4.0 |
50 |
1.08 |
1.06 |
1.04 |
1.03 |
1.00 |
0.96 |
0.90 |
0.85 |
0.81 |
0.77 |
0.74 |
70 |
1.08 |
1.06 |
1.05 |
1.03 |
1.00 |
0.96 |
0.90 |
0.84 |
0.80 |
0.76 |
0.73 |
95 |
1.08 |
1.07 |
1.05 |
1.03 |
1.00 |
0.95 |
0.89 |
0.84 |
0.80 |
0.75 |
0.72 |
120 |
1.09 |
1.07 |
1.05 |
1.03 |
1.00 |
0.95 |
0.89 |
0.83 |
0.79 |
0.75 |
0.71 |
150 |
1.09 |
1.07 |
1.05 |
1.03 |
1.00 |
0.95 |
0.88 |
0.83 |
0.79 |
0.74 |
0.71 |
185 |
1.09 |
1.07 |
1.05 |
1.03 |
1.00 |
0.95 |
0.88 |
0.83 |
0.78 |
0.74 |
0.70 |
240 |
1.10 |
1.08 |
1.05 |
1.04 |
1.00 |
0.95 |
0.88 |
0.82 |
0.78 |
0.73 |
0.70 |
300 |
1.10 |
1.08 |
1.06 |
1.04 |
1.00 |
0.95 |
0.87 |
0.82 |
0.77 |
0.72 |
0.69 |
400 |
1.11 |
1.08 |
1.06 |
1.04 |
1.00 |
0.94 |
0.87 |
0.82 |
0.77 |
0.72 |
0.68 |
500 |
1.12 |
1.08 |
1.06 |
1.04 |
1.00 |
0.94 |
0.87 |
0.81 |
0.76 |
0.71 |
0.68 |
630 |
1.12 |
1.09 |
1.06 |
1.04 |
1.00 |
0.94 |
0.87 |
0.81 |
0.76 |
0.71 |
0.67 |
800 |
1.13 |
1.10 |
1.07 |
1.04 |
1.00 |
0.94 |
0.86 |
0.80 |
0.75 |
0.71 |
0.67 |
1000 |
1.13 |
1.10 |
1.07 |
1.04 |
1.00 |
0.94 |
0.86 |
0.80 |
0.75 |
0.70 |
0.66 |