Three /Four Core Copper, PVC Insulated Armoured /Unarmoured Cables
Current Rating & Voltage drop for cables & wires Upto and Including 600/1000V
3 and 4 Core Copper, PVC Insulated Armoured /Unarmoured Cables;
Nominal Area of Conductor |
In Air |
In Ground |
In Duct |
Voltage drop |
Unarmoured |
Armoured |
Armoured |
Armoured |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
Sqmm |
A |
A |
A |
V/A/Km |
V/A/Km |
1.5 |
20 |
23 |
20 |
23 |
26 |
30 |
21 |
24 |
26.3 |
26.3 |
2.5 |
28 |
33 |
27 |
32 |
33 |
38 |
27 |
31 |
16.1 |
16.1 |
4 |
35 |
41 |
35 |
41 |
45 |
51 |
36 |
41 |
10.0 |
10.0 |
6 |
45 |
53 |
45 |
53 |
56 |
64 |
45 |
52 |
6.7 |
6.7 |
10 |
59 |
69 |
62 |
73 |
74 |
84 |
61 |
69 |
4.0 |
4.0 |
16 |
78 |
90 |
81 |
93 |
96 |
107 |
79 |
88 |
2.4 |
2.5 |
25 |
104 |
119 |
109 |
125 |
126 |
140 |
102 |
113 |
1.51 |
1.59 |
35 |
127 |
145 |
133 |
152 |
151 |
168 |
123 |
137 |
1.10 |
1.15 |
50 |
155 |
178 |
161 |
184 |
179 |
199 |
145 |
162 |
0.82 |
0.85 |
70 |
197 |
225 |
204 |
233 |
221 |
246 |
181 |
202 |
0.57 |
0.60 |
95 |
244 |
280 |
252 |
289 |
265 |
295 |
217 |
242 |
0.42 |
0.44 |
120 |
283 |
324 |
291 |
333 |
302 |
336 |
248 |
275 |
0.34 |
0.36 |
150 |
323 |
368 |
333 |
379 |
338 |
374 |
278 |
307 |
0.29 |
0.30 |
185 |
374 |
430 |
382 |
439 |
382 |
427 |
315 |
353 |
0.25 |
0.25 |
240 |
445 |
510 |
451 |
517 |
440 |
490 |
364 |
405 |
0.21 |
0.21 |
300 |
511 |
586 |
512 |
587 |
493 |
550 |
407 |
455 |
0.18 |
0.19 |
400 |
592 |
680 |
588 |
675 |
552 |
616 |
466 |
522 |
0.16 |
0.17 |
Installation conditions for above Rating:
Maximum Conductor Temp. for PVC Type 5 Insulation 85oC
Maximum Conductor Temp. for PVC TI1/Type A Insulation 70oC
Ambient Air Temperature 30oC
Ground Temperature 20oC
Depth of Laying 0.5m
Thermal Resitivity of soil 1.2 K.m/w