Nominal Area of Conductor Maximum Conductor Resistance at 20°C Thickness of Insulation Thickness of Outer Sheath Approx. Overall Diameter Approx. Cable Weight Standard Packing Length Drum Size Approx. Gross Weight 
Phase Neutral Phase Neutral Phase Neutral
Sqmm Ohm/Km mm mm mm Kg/Km Metre ± 10%   KG
25  16 0.727 1.15 0.9 0.7 1.8 22.0 1090 500 D-10 605
35 16 0.524 1.15 0.9 0.7 1.8 25.4 1410 500 D-12 815
50 25 0.387 0.727 1.0 0.9 1.8 28.3 1890 500 D-12 1060
70 35 0.268 0.524 1.1 0.9 1.9 31.8 2610 500 D-14 1460
 
95  50 0.193 0.387 1.1 1.0 2.1 36.3 3540 500 D-18 2010
120 70 0.153 0.268 1.2 1.1 2.2 39.7 4480 500 D-18 2480
150 70 0.124 0.268 1.4 1.1 2.3 44.6 5440 500 D-18 2960
 
185  95 0.0991 0.193 1.6 1.1 2.5 49.5 6780 250 D-16 1910
240 120 0.0754 0.153 1.7 1.2 2.7 54.6 8660 250 D-18 2405
300 150 0.0601 0.124 1.8 1.4 2.9 60.4 10850 250 D-18 2950
 
 400 185 0.0470 0.0991 2.0 1.6 3.1 67.6 13900 200 D-18 3020
500 250 0.0366 0.0754 2.2 1.7 3.4 76.7 17400 200 D-22 3950

All phase conductors 25 Sqmm and above shaped stranded (Class 2).
All neutral conductors circular stranded (Class 2).
Cables conform to IEC 60502-1.