Low Voltage Cables/ XLPE Insulated Low Voltage Cables/Four Core Cables Cu/XLPE/PVC/SWA/PVC & Cu/XLPE/SWA/PVC 


Four Core Cables Cu/XLPE/PVC/SWA/PVC & Cu/XLPE/SWA/PVC 

600/1000 V - FOUR CORE

Copper Conductor

XLPE Insulated Steel Wire Armoured

PVC Sheathed Cables

(CU/XLPE/PVC/SWA/PVC and CU/XLPE/SWA/PVC)


Nominal
Area
of Conductor
Max. Conductor Resistance
at 20°C
Thickness
of
Insulation
Thickness of Bedding Diameter of Armour Wire Thickness of
Outer Sheath
Approx. Overall Diameter Approx. Cable Weight  Standard Packing
Length 
Drum Size  Approx. Gross Weight
Extruded

Lapped Bedding

Extruded Bedding Lapped Bedding Extruded Bedding Lapped Bedding Extruded Bedding Lapped Bedding
Sqmm Ohm/Km mm mm mm mm mm Kg/Km Metre
±10%
  Kg
    1.5*   12.1 0.7 1.0 - 0.9 1.8 15.5 - 430 - 1000 D-10  490 -
1.5 12.1 0.7 1.0 - 0.9 1.8 16.0 - 440 - 1000 D-11 540 -
  2.5* 7.41 0.7 1.0 - 0.9 1.8 16.5 - 490 - 1000 D-11 590 -
2.5 7.41 0.7 1.0 - 0.9 1.8 17.0 - 510 - 1000 D-11 610 -
 
  4   4.61 0.7 1.0 - 0.9 1.8 18.2 - 610 - 1000 D-12 720 -
6 3.08 0.7 1.0 - 1.25 1.8 20.3 - 840 - 100 D-12 950 -
10 1.83 0.7 1.0 - 1.25 1.8 22.7 - 1090 - 1000 D-14 1240 -
 
  16 1.15 0.7 1.0 - 1.6 1.8 25.9 - 1560 - 1000 D-16 1770 -
  25 0.727 0.9   1.0 0.8 1.6 1.8 26.6 25.5 1870 1775 500 D-12 1045 995
 35 0.524 0.9 1.0 0.8 1.6 1.9 30.2 29.1 2380 2270 500 D-12 1300 1245
 
  50   0.387 1.0 1.0 0.8 1.6 2.0 33.3 32.2 2990 2840 500 D-16 1705 1630
70 0.268 1.1 1.2 0.8 2.0 2.3 38.3 36.8 4210 3995 500 D-18 2345 2240
 95 0.193 1.1 1.2 0.8 2.0 2.3 42.5 41.0 5390 5155 500 D-18 2935 2820
 
120 0.153 1.2 1.4 0.8 2.5 2.5 47.5 45.6 6950 6640 500 D-19 3795 3640
150 0.124 1.4 1.4 0.8 2.5 2.6 52.4 49.8 8380 7985 500 D-19 4510 4310
185 0.0991 1.6 1.4 0.8 2.5 2.8 57.3 55.4 10030 9650 250 D-18 2745 2655
 
240 0.0754 1.7 1.6 0.8 2.5 3.0 62.8 60.5 12500 12025 250 D-18 3365 3245
300 0.0601 1.8 1.6 0.8 2.5 3.2 68.6 66.3 15200 14655 250 D-21 4220 4085
400 0.0470 2.0 1.8 0.8 3.15 3.5 77.7 75.0 19950 19145 200 D-22 4460 4300
 
500 0.0366 2.2 1.8 0.8 3.15 3.8 86.8 86.1 24460 23590 200 D-21 5310 5140

* Circular solid conductors (Class 1).
   Conductors including 16 Sqmm circular stranded (Class 2).
   25 Sqmm and above shaped stranded conductors (Class 2).
   Cables conform to IEC 60502 - 1.
   Drum size given above are for cables with extruded bedding.