Soft Drawn Bare Copper Conductors (SDBC)
Conductors For Earthing Purposes
Soft Drawn Bare Copper Conductors
(SDBC)
Nominal Area
Of Conductor
|
Minimum Number of Wires in the Conductor |
Approx. Conductor Diameter |
Maximum Conductor Resistance at 20°C |
Approx. Conductor
Weight
|
Standard Packing Length |
Drum size |
Approx. Gross weight |
Sqmm |
No./mm |
mm |
Ohm/km |
Kg/Km |
Meter±5% |
|
KG |
4* |
7 |
2.52 |
4.61 |
34.0 |
2000 |
D-6 |
115 |
6* |
7 |
3.08 |
3.08 |
51.0 |
2000 |
D-6 |
145 |
10 |
7 |
3.8 |
1.83 |
87.0 |
2000 |
D-6 |
220 |
|
16 |
6 |
4.9 |
1.15 |
136 |
2000 |
D-6 |
315 |
25 |
6 |
6.0 |
0.727 |
215 |
2000 |
D-7 |
475 |
35 |
6 |
7.1 |
0.524 |
301 |
1000 |
D-7 |
345 |
|
50 |
6 |
8.2 |
0.387 |
410 |
1000 |
D-7 |
455 |
70 |
12 |
9.8 |
0.268 |
594 |
1000 |
D-8 |
645 |
95 |
15 |
11.7 |
0.193 |
820 |
1000 |
D-11 |
920 |
|
120 |
18 |
13.2 |
0.153 |
1040 |
1000 |
D-12 |
1150 |
150 |
18 |
14.6 |
0.124 |
1300 |
1000 |
D-12 |
1410 |
185 |
30 |
16.2 |
0.0991 |
1615 |
1000 |
D-14 |
1770 |
|
240 |
34 |
18.7 |
0.0754 |
2100 |
1000 |
D-16 |
2310 |
300 |
34 |
20.7 |
0.0601 |
2650 |
1000 |
D-18 |
2890 |
400 |
53 |
23.6 |
0.0470 |
3440 |
1000 |
D-18 |
3680 |
* Conductors circular Stranded (Class 2).
All other conductors circular stranded compacted (Class 2).
Conductors conform to BS 6360 /BS EN 60228 and IEC 60228.
Non - compacted untinned or tinned conductors available on Request.