Over Head Lines Cables/ Conductors for Earthing/Soft Drawn Bare Copper Conductors (SDBC)


Soft Drawn Bare Copper Conductors (SDBC)

Conductors For Earthing Purposes

Soft Drawn Bare Copper Conductors

(SDBC)


Nominal  Area

Of Conductor

Minimum Number  of Wires in the Conductor Approx. Conductor Diameter Maximum Conductor Resistance  at 20°C

Approx.  Conductor

Weight

Standard Packing Length Drum size Approx. Gross weight
Sqmm    No./mm  mm  Ohm/km  Kg/Km  Meter±5%    KG 
 4*  7  2.52  4.61 34.0  2000  D-6  115 
 6* 7 3.08  3.08 51.0  2000  D-6  145 
 10  7 3.8 1.83  87.0 2000  D-6  220
        
16  6 4.9  1.15  136  2000  D-6 315 
25 6 6.0  0.727  215 2000   D-7  475 
35 6  7.1  0.524  301  1000  D-7  345 
        
 50  6 8.2  0.387   410  1000   D-7  455 
 70  12 9.8  0.268  594 1000  D-8 645
 95 15 11.7 0.193   820 1000     D-11   920 
        
 120 18    13.2    0.153  1040  1000   D-12 1150
 150 18   14.6  0.124 1300  1000    D-12  1410
 185 30  16.2    0.0991 1615  1000   D-14 1770
        
 240 34 18.7   0.0754 2100  1000 D-16  2310 
 300  34  20.7  0.0601 2650 1000  D-18  2890
 400 53 23.6  0.0470 3440  1000  D-18   3680 

* Conductors circular Stranded (Class 2).
   All other conductors circular stranded compacted (Class 2).
   Conductors conform to BS 6360  /BS EN 60228 and IEC 60228.
   Non - compacted untinned or tinned conductors available on Request.