Current Rating & Voltage drop for cables & wires Upto and Including 600/1000V
3 and 4 Core Aluminium ,PVC Insulated Armoured /Unarmoured Cables;
Nominal Area of Conductor |
In Air |
In Ground |
In Duct |
Voltage drop |
Unarmoured |
Armoured |
Armoured |
Armoured |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
at 70oC |
at 85oC |
Sqmm |
A |
A |
A |
V/A/Km |
V/A/Km |
16 |
59 |
67 |
62 |
71 |
74 |
82 |
60 |
67 |
4.00 |
4.18 |
2.5 |
78 |
89 |
80 |
92 |
95 |
106 |
77 |
86 |
2.50 |
2.62 |
35 |
95 |
108 |
98 |
112 |
114 |
126 |
93 |
102 |
1.81 |
1.91 |
50 |
116 |
133 |
120 |
137 |
136 |
151 |
111 |
123 |
1.34 |
1.41 |
70 |
148 |
169 |
151 |
173 |
168 |
187 |
137 |
152 |
0.93 |
0.98 |
95 |
183 |
209 |
188 |
215 |
202 |
225 |
165 |
184 |
0.68 |
0.71 |
120 |
211 |
242 |
217 |
248 |
231 |
257 |
189 |
211 |
0.54 |
0.57 |
150 |
244 |
279 |
248 |
283 |
259 |
288 |
212 |
236 |
0.45 |
0.47 |
185 |
280 |
320 |
287 |
328 |
294 |
327 |
242 |
270 |
0.37 |
0.38 |
240 |
335 |
383 |
343 |
392 |
343 |
381 |
283 |
315 |
0.29 |
0.31 |
300 |
386 |
440 |
395 |
450 |
388 |
430 |
321 |
355 |
0.25 |
0.26 |
400 |
431 |
493 |
431 |
493 |
420 |
467 |
340 |
377 |
0.21 |
0.22 |
Installation conditions for above Rating:
Maximum Conductor Temp. for PVC Type 5 Insulation 85oC
Maximum Conductor Temp. for PVC TI1/Type A Insulation 70oC
Ambient Air Temperature 30oC
Ground Temperature 20oC
Depth of Laying 0.5m
Thermal Resitivity of soil 1.2 K.m/w