Over Head Lines Cables/ Overhead Transmission Conductors/All Aluminium Alloy Conductors (AAAC)


All Aluminium Alloy Conductors (AAAC)

Conductors For OverHead Lines

All Aluminium Alloy Conductors

(AAAC)


CODE Nominal Area of Conductor  No. and Nominal Diameter of Wires Approx. Overall Diameter Calculated D.C Resistance at 20°C(Max.) Approx. Weight of Conductor Breaking Load Standard Packing Length Drum size Approx. Gross weight
  Sqmm  No./mm mm Ohm/km Kg/Km KN  Meter ± 5%   KG 
BOX 18.8 7/1.85 5.55 1.7480 51.4 5.55 2000 D-6 148
 ACACIA  23.8 7/2.08  6.24 1.3828 64.9 7.02 2000 D-7 175
 ALMOND  30.1   7/2.34  7.02 1.0926 82.2  8.88   2000 D-8 214
 
 CEBAR  35.5  7/2.54   7.62  0.9273 96.8 10.46  2000  D-8  244 
 DEODAR  42.2  7/2.77  8.31 0.7797 151.2 12.44  2000  D-9 290
 FIR  47.8 7/2.95  8.85 0.6875 130.6 14.11  2000  D-9  321 
 
 HAZEL  59.9  7/3.30  9.90 0.5494 163.4 17.66  2000  D-9   387  
 PINE  71.6  7/3.61  10.80 0.4591 195.6 21.14  2000  D-10 451
 HOLLY  84.1  7/3.91  11.70 0.3913 229.5 24.79  2000  D-11  559 
 
 WILLOW  89.7  7/4.04  12.10 0.3665 245.0 26.47  2000  D-11  590
 OAK  118.9  7/4.65   14.00  0.2767 324.5 35.07  2000  D-12   759 
 MULBERRY  150.9  19/3.18  15.90 0.2192 414.3 44.52  2000   D-14   979
  
 ASH  180.7  19/3.48  17.40  0.1830 496.1 53.31  2000  D-14  1142
 ELM  211  19/3.76  18.80 0.1568 579.2 62.24  2000  D-16  1368
 POPLAR  239.4   37/2.87   20.10 0.1387 659.4 70.61  2000  D-18  1559
 
 SYCAMORE  303.2   37/3.23    22.60   0.1095 835.2 89.40  2000   D-18  1910
 UPAS  362.1  37/3.53  24.70  0.0917 997.5 106.82 2000  D-18  2235
 YEW  479  37/4.06  28.40   0.0693  1319.6 141.31  2000  D-21   3059 
       
 TOTARA  798.1  37/4.14  29.00  0.0666 1372.1 146.93   2000   D-21  3164
 RUBUS  586.9  61/3.50  31.50  0.0567 1622.0 173.13  2000  D-22  3714
 SORBUS  659.4  61/3.71  33.40  0.0505 1822.5 194.53  2000  D-23  4145
 
ARAUCARIA   821.1  61/4.14  37.30  0.0406 2269.4 242.24  2000  D-23   5093 
 REDWOOD  996.2  61/4.56  41.00  0.0334 2753.2 293.88  2000  D-23  6006

AAAC - conform to BS EN 50182 - 2001.