Over Head Lines Cables/ Overhead Transmission Conductors/All Aluminium Conductors (AAC)


All Aluminium Conductors (AAC)

Conductors For Overhead Lines

All Aluminium Conductors

(AAC)


CODE Nominal Aluminium Area Stranding: No. and Nominal Diameter of Wires Approx. Overall Diameter

Calculated DC Resistance at 20°C(Max.)

Approx. Weight of Conductor Breaking Load Standard Packing Length Drum size Approx. Gross weight
   Sqmm    No./mm  mm  Ohm/km  Kg/Km  KN  Meter ± 10%      KG 
MIDGE   22  7/2.06  6.18  1.227 64 3.99   2000  D-7  175
ANT 50 7/3.10 9.30  0.5419 145 8.28 2000 D-9 350
FLY  60  7/3.40   10.20   0.4505  174  9.90   2000  D-9  410
 
 WASP 100 7/4.39   13.17 0.2702  290  16.00  2000  D-11   680 
 HORNET 150   19/3.25   16.25 0.1825 434  25.70  2000  D-14   1020
CHAFER  200  19/3.78  18.90  0.1349 587  32.40  2000  D-16   1380
 
COCKROACH  250   19/4.22  21.10  0.1083 731  40.40  2000  D-18  1700 
BUTTERFLY  300  19/4.65 23.25  0.08916  888 48.75 2000  D-18  2020 
 CENTIPEDE 400    37/3.78  26.46  0.06944 1145  63.10  2000  D-19  2610 

AAC conform to BS 215 (Part1) 1970.