Lead Sheathed Cables/ XLPE Insulated 1.9/3.3 KV Cables/Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC


Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC

1.9/3.3 KV - THREE CORE

COPPER CONDUCTOR XLPE INSULATED
LEAD SHEATHED
STEEL WIRE ARMOURED
PVC SHEATHED CABLES
CU/XLPE/PVC/LC/PVC/SWA/PVC


Nominal Area of Conductor Maximum Conductor Resistance at 20°C

Thickness of Insulation(Nom.)

Thickness of Extruded Bedding(Approx.) Thickness of Lead Sheath(Nom.) Thickness of Seperation Sheath(Nom.) Dia of Armour wire(Nom.) Thickness of Outer Sheath(Nom.)  Approx. Overall Diameter  Approx. Cable Weight Standard Packing Length Drum Size Approx. Gross weight
 Sqmm Ohm/KM mm mm mm mm mm mm  mm Kg/Km  Metre±5%      kg 
25 0727 2.0 1.0 1.2 1.1 2.00 2.1 35.8 3515 500 D-18 2000
35 0.524 2.0 1.0 1.3 1.1 2.00 2.1 38.3 4135 500 D-18 2310
50 0.387 2.0 1.2 1.4 1.2 2.00 2.3 42.3 5030 500 D-18 2755
 
70 0.268 2.0 1.2 1.5 1.3 2.50 2.4 46.0 6345 500 D-19 3495
95 0.193 2.0 1.2 1.6 1.3 2.50 2.5 50.2 7715 500 D-19 4180
120 0.153 2.0 1.4 1.7 1.4 2.50 2.7 54.4 9105 500 D-21 4975
 
150 0.124 2.0 1.4 1.8 1.5 2.50 2.8 57.1 10385 250 D-18 2840
185 0.0991 2.0 1.4 1.9 1.5 2.50 2.9 60.9 12010 250 D-18 3245
240 0.0754 2.0 1.6 2.0 1.6 2.50 3.1 67.4 14630 250 D-18 3900
 
300 0.0601 2.0 1.6 2.2 1.7 2.50 3.3 72.2 17375 250 D-21 4765
400 0.0470 2.0 1.6 2.4 1.9 3.15 3.6 81.1 22195 200 D-21 4860
500 0.0366 2.2 1.8 2.6 2.0 3.15 3.8 87.3 26470 200 D-23 5795

All Conductors Shaped starnded conductors (Class 2).
Extruded PVC Bedding above and below Lead Sheath.
Lead Alloy Type - 'E' to BS 801, Lead Sheath Thickness to IEC 60502-1/1997
PVC Type - 9 / ST - 2 Outersheath
Cables conform to IEC 60502-1/1997.