Four Core Cables with reduced Neutral Al/XLPE/PVC/SWA/PVC & Al/XLPE/SWA/PVC
600/1000 V - FOUR CORE WITH REDUCED NEUTRAL
Aluminium Conductor
XLPE Insulated Steel Wire Armoured
PVC Sheathed Cables
(Al/XLPE/PVC/SWA/PVC and Al/XLPE/SWA/PVC)
Nominal Area of Conductor |
Max. Conductor Resistance at 20°c |
Thickness of Insulation |
Thickness of Bedding |
Diameter of Armour Wire |
Thickness of Outer Sheath |
Approx. Overall Diameter |
Approx. Cable Weight |
Standard Packing Length |
Drum Size |
Approx. Gross Weight |
Extruded Bedding |
Lapped Bedding |
Extruded Bedding |
Lapped Bedding |
Extruded Bedding |
Lapped Bedding |
Phase |
Neutral |
Phase |
Neutral |
Phase |
Neutral |
Extruded |
Lapped |
Sqmm |
Ohm/Km |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
Metre ± 10% |
|
Kg |
35 |
16 |
0.868 |
1.91 |
0.9 |
0.7 |
1.0 |
0.8 |
1.6 |
1.8 |
29.7 |
28.6 |
1480 |
1350 |
500 |
D-12 |
850 |
785 |
50 |
25 |
0.641 |
1.20 |
1.0 |
0.9 |
1.0 |
0.8 |
1.6 |
1.9 |
33.1 |
32.0 |
1780 |
1640 |
500 |
D-16 |
1100 |
1030 |
70 |
35 |
0.443 |
0.868 |
1.1 |
0.9 |
1.2 |
0.8 |
2.0 |
2.1 |
38.0 |
36.5 |
2480 |
2270 |
500 |
D-18 |
1480 |
1380 |
95 |
50 |
0.320 |
0.641 |
1.1 |
1.0 |
1.2 |
0.8 |
2.0 |
2.2 |
42.1 |
40.6 |
2980 |
2750 |
500 |
D-18 |
1730 |
1620 |
|
120 |
70 |
0.253 |
0.443 |
1.2 |
1.1 |
1.2 |
0.8 |
2.0 |
2.3 |
45.7 |
44.2 |
3460 |
3220 |
500 |
D-19 |
2050 |
1930 |
150 |
70 |
0.206 |
0.443 |
1.4 |
1.1 |
1.4 |
0.8 |
2.5 |
2.5 |
50.4 |
48.5 |
4440 |
4100 |
500 |
D-19 |
2540 |
2370 |
185 |
95 |
0.164 |
0.320 |
1.6 |
1.1 |
1.4 |
0.8 |
2.5 |
2.7 |
56.4 |
54.5 |
5270 |
4910 |
500 |
D-21 |
3060 |
2880 |
|
240 |
120 |
0.125 |
0.253 |
1.7 |
1.2 |
1.6 |
0.8 |
2.5 |
2.9 |
62.8 |
60.5 |
6370 |
5880 |
500 |
D-22 |
3660 |
3410 |
300 |
150 |
0.100 |
0.206 |
1.8 |
1.4 |
1.6 |
0.8 |
2.5 |
3.0 |
68.2 |
65.9 |
7450 |
6920 |
300 |
D-20 |
2660 |
2430 |
300* |
185 |
0.100 |
0.164 |
1.8 |
1.6 |
- |
0.8 |
2.5 |
2.7 |
- |
65.7 |
- |
6970 |
300 |
D-19 |
- |
2410 |
|
300 |
185 |
0.100 |
0.164 |
1.8 |
1.6 |
1.6 |
0.8 |
2.5 |
3.1 |
68.4 |
66.1 |
7560 |
7030 |
250 |
D-18 |
2130 |
2000 |
400 |
185 |
0.0778 |
0.164 |
2.0 |
1.6 |
1.6 |
0.8 |
3.15 |
3.3 |
76.9 |
74.6 |
9750 |
9110 |
250 |
D-19 |
2760 |
2600 |
All phase conductors shaped stranded (Class 2).
All Neutral conductors circular stranded (Class 2).
Cables conform to IEC 60502 - 1, *Cable as per MEW Kuwait specification.
Drum size shown above are for cables with extruded bedding.