Low Voltage Cables/Current Ratings And Voltage Drop List/Rating Factors for variation in Thermal Resistivity of Soil for Three Single core Cables laid Direct in Ducts


Rating Factors for variation in Thermal Resistivity of Soil for Three Single core Cables cables laid Direct in Ducts:

Nominal Area of Conductor mm²

Thermal Resistivity of Soil in K.m/W
  0.7  0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0
50 1.11 1.08 1.06 1.04 1.0 0.94 0.87 0.82 0.77 0.73 0.69
70 1.12 1.09 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.72 0.68
95 1.12 1.09 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.72 0.68
120 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.72 0.67
150 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.71 0.67
185 1.13 1.10 1.07 1.04 1.0 0.93 0.86 0.79 0.75 0.70 0.67
240 1.14 1.11 1.07 1.04 1.0 0.93 0.86 0.79 0.74 0.70 0.66
300 1.14 1.11 1.08 1.05 1.0 0.93 0.85 0.79 0.74 0.69 0.65
400 1.14 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.68 0.65
500 1.15 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.68 0.64
630 1.15 1.12 1.09 1.05 1.0 0.93 0.84 0.78 0.72 0.68 0.64
800 1.16 1.12 1.09 1.05 1.0 0.93 0.84 0.77 0.72 0.67 0.64
1000 1.16 1.13 1.09 1.05 1.0 0.92 0.84 0.77 0.71 0.67 0.63