Low Voltage Cables/Current Ratings And Voltage Drop List/Two Core Aluminium, PVC Insulated Armoured /Unarmoured Cables


Two Core Aluminium, PVC Insulated Armoured /Unarmoured Cables

Current Rating & Voltage drop for cables & wires Upto and Including 600/1000V

Two Core Aluminium, PVC Insulated Armoured /Unarmoured Cables


Nominal Area of Conductor In Air   In Ground In Duct Voltage drop
Unarmoured  Armoured   Armoured  Armoured 
at 70oC at 85oC at 70o at 85oC at 70o at 85oC at 70o at 85oC at 70o at 85oC

 Sqmm

A     A  A V/A/Km  V/A/Km 
 16  70 80  73   83  87  97 71  79  4.6  4.8 
25  90  103  92  105  112  125  92  102  2.89  3.02 
35  109  124  112  128  136  151  109  121  2.09  2.21 
50  134  153  136  156  159  177  131  146  1.55  1.63 
70  169  194  174  199  199  222  162  180  1.08  1.13 
95  209  239  213  244  238  265  194  215  0.79  0.82 
120 241  276  241  276  261  291  227  253  0.63  0.66 
150  276  315  276  315  299  332  251  279  0.52  0.54 
185  316  362  316  362  342  380  288  319  0.42  0.44 
240  374  427  374  427  397  441  330  368  0.34  0.35 
300  419  478  419  478  441  489  365  404  0.28  0.30 
400  482  551  482  551  478  531  418  466  0.24  0.25 

Installation conditions for above Rating:

Maximum Conductor Temp. for PVC Type 5 Insulation       85oC

Maximum Conductor Temp. for PVC TI1/Type A Insulation 70oC

Ambient Air Temperature                                                30oC

Ground Temperature                                                      20oC

Depth of Laying                                                             0.5m

Thermal Resitivity of soil                                                1.2 K.m/w