Medium Voltage Cables/XLPE Insulated Medium Voltage Cables/Single Core Cables 19/33 KV (Cu/SC/XLPE/SC/CuT/PVC/AWA/PVC)


Single Core Cables 19/33 KV (Cu/SC/XLPE/SC/CuT/PVC/AWA/PVC)

19/33 KV - SINGLE CORE

(HIGHEST SYSTEM VOLTAGE - 36 KV)

COPPER CONDUCTOR XLPE INSULATED

COPPER TAPE SCREENED

ALUMINIUM WIRE ARMOURED

PVC SHEATHED CABLES

(CU/SC/XLPE/SC/CUT/PVC/AWA/PVC)


Nominal Area of Conductor Maximum Conductor Resistance  at 20°C   Thickness of XLPE Insulation Thickness of Copper Tape Thickness of Extruded Bedding Dia of Armour Wire Thickness of Outer Sheath Approx.  Overall Diameter Approx. Cable Weight Standard Packing Length Drum size Approx. Gross Weight
Sqmm Ohm/Km mm mm mm mm mm mm Kg/Km Metre ± 10%   Kg
50 0.387 8.0 0.075 1.2 2.0 2.2 39.4 2050 500 D-18 1270
70 0.268 8.0 0.075 1.2 2.0 2.2 41.0 2330 500 D-18 1410
95 0.193 8.0 0.075 1.2 2.0 2.3 43.1 2710 500 D-18 1600
                       
120 0.153 8.0 0.075 1.2 2.0 2.3 44.6 3020 500 D-18 1750
150 0.124 8.0 0.075 1.3 2.5 2.4 47.4 3570 500 D-19 2110
185 0.0991 8.0 0.075 1.3 2.5 2.5 49.2 3990 500 D-19 2320
                       
240 0.0754 8.0 0.075 1.3 2.5 2.5 51.7 4670 500 D-19 2660
300 0.0601 8.0 0.075 1.4 2.5 2.6 54.1 5410 500 D-21 3130
400 0.0470 8.0 0.075 1.4 2.5 2.7 57.2 6430 500 D-22 3690
                       
500 0.0366 8.0 0.075 1.5 2.5 2.8 60.6 7620 500 D-22 4280
630 0.0283 8.0 0.075 1.6 2.5 2.9 64.8 8935 500 D21M 4890

All conductors circular compacted.
Equivalant voltage designation as per IEC 60502 - 2 : 18/30 KV.
Cables conform to IEC 60502 - 2