Low Voltage Cables/XLPE Insulated Low Voltage Cables/Three Core Cables Cu/XLPE/PVC


Three Core Cables Cu/XLPE/PVC

600/1000 V - THREE CORE

Copper Conductor XLPE Insulated

PVC Sheathed Cables

(Cu/XLPE/PVC)


Nominal Area of Conductor Maximum Conductor Resistance  at 20°C  Thickness of Insulation  Thickness of Outer Sheath Approx. Overall Diameter Approx. Cable Weight Standard Packing Length Drum Size Approx. Gross Weight
Sqmm Ohm/Km mm mm mm Kg/Km Metre ±10%   Kg
  1.5* 12.1 0.7 1.8 11.3 170 1000 D-9 230
1.5 12.1 0.7 1.8 11.7 175 1000 D-9 235
  2.5* 7.41 0.7 1.8 12.2 210 1000 D-9 270
2.5 7.41 0.7 1.8 12.6 220 1000 D-9 280
 
4 4.61 0.7 1.8 13.7 280 1000 D-10 340
6 3.08 0.7 1.8 15.0 360 1000 D-10 420
10 1.83 0.7 1.8 16.5 500 1000 D-11 600
 
16 1.15 0.7 1.8 18.9 705 1000 D-12 815
25 0.727 0.9 1.8 19.9 955 500 D-10 540
35 0.524 0.9 1.8 22.3 1250 500 D-11 725
 
50 0.387 1.0 1.8 25.5 1610 500 D-12 915
70 0.268 1.1 1.9 28.2 2230 500 D-12 1230
95 0.193 1.1 2.0 32.2 3000 500 D-16 1710
 
120 0.153 1.2 2.1 35.8 3750 500 D-18 2120
150 0.124 1.4 2.2 39.0 4640 500 D-18 2560
185 0.0991 1.6 2.4 43.6 5730 250 D-14 1580
 
240 0.0754 1.7 2.6 49.6 7360 250 D-16 2050
300 0.0601 1.8 2.7 54.2 9190 250 D-18 2540
400 0.0470 2.0 3.0 61.8 11850 250 D-18 3200

* Circular solid conductor (Class 1).
   Conductors including 16 Sqmm circular stranded (Class 2).
   25 Sqmm and above shaped stranded conductors (Class 2).
   Cables upto 10 Sqmm conform to IEC 60502-1.
   All other cables conform generally to BS 5467 and IEC 60502-1.