We build cables for life 88
Rating Factors for variation in Thermal Resistivity of Soil for Twin or Multi-core Cables laid Direct in the Ground

Nominal Area of Conductor mm² 

Thermal Resistivity of Soil in K.m/W
  0.7 0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0
1.5/ 2.5 1.12 1.09 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.70 0.66
4 1.13 1.10 1.07 1.05 1.0 0.94 0.85 0.79 0.74 0.69 0.65
6 1.14 1.10 1.07 1.05 1.0 0.93 0.85 0.79 0.74 0.68 0.64
10 1.15 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.67 0.63
16 1.16 1.12 1.08 1.05 1.0 0.93 0.84 0.77 0.72 0.66 0.62
25 1.17 1.13 1.09 1.05 1.0 0.93 0.83 0.77 0.71 0.65 0.61
35 1.17 1.13 1.09 1.06 1.0 0.92 0.83 0.76 0.71 0.65 0.61
50 1.17 1.13 1.09 1.06 1.0 0.92 0.83 0.76 0.71 0.65 0.61
70 1.18 1.14 1.09 1.06 1.0 0.92 0.83 0.75 0.70 0.64 0.60
95 1.18 1.14 1.09 1.06 1.0 0.92 0.83 0.75 0.70 0.64 0.60
120 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.75 0.69 0.63 0.59
150 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.75 0.69 0.63 0.59
185 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.74 0.69 0.63 0.59
240 1.20 1.15 1.10 1.07 1.0 0.92 0.81 0.74 0.69 0.63 0.59
300 1.20 1.15 1.10 1.07 1.0 0.92 0.81 0.74 0.69 0.63 0.59
400 1.20 1.15 1.10 1.07 1.0 0.92 0.81 0.74 0.69 0.63 0.59