Rating Factors for variation in Thermal Resistivity of Soil for Twin or Multi-core Cables laid Direct in the Ground
Nominal Area of Conductor mm²
|
Thermal Resistivity of Soil in K.m/W |
|
0.7 |
0.8 |
0.9 |
1.0 |
1.2 |
1.5 |
2.0 |
2.5 |
3.0 |
3.5 |
4.0 |
1.5/ 2.5 |
1.12 |
1.09 |
1.07 |
1.04 |
1.0 |
0.94 |
0.86 |
0.80 |
0.75 |
0.70 |
0.66 |
4 |
1.13 |
1.10 |
1.07 |
1.05 |
1.0 |
0.94 |
0.85 |
0.79 |
0.74 |
0.69 |
0.65 |
6 |
1.14 |
1.10 |
1.07 |
1.05 |
1.0 |
0.93 |
0.85 |
0.79 |
0.74 |
0.68 |
0.64 |
10 |
1.15 |
1.11 |
1.08 |
1.05 |
1.0 |
0.93 |
0.85 |
0.78 |
0.73 |
0.67 |
0.63 |
16 |
1.16 |
1.12 |
1.08 |
1.05 |
1.0 |
0.93 |
0.84 |
0.77 |
0.72 |
0.66 |
0.62 |
25 |
1.17 |
1.13 |
1.09 |
1.05 |
1.0 |
0.93 |
0.83 |
0.77 |
0.71 |
0.65 |
0.61 |
35 |
1.17 |
1.13 |
1.09 |
1.06 |
1.0 |
0.92 |
0.83 |
0.76 |
0.71 |
0.65 |
0.61 |
50 |
1.17 |
1.13 |
1.09 |
1.06 |
1.0 |
0.92 |
0.83 |
0.76 |
0.71 |
0.65 |
0.61 |
70 |
1.18 |
1.14 |
1.09 |
1.06 |
1.0 |
0.92 |
0.83 |
0.75 |
0.70 |
0.64 |
0.60 |
95 |
1.18 |
1.14 |
1.09 |
1.06 |
1.0 |
0.92 |
0.83 |
0.75 |
0.70 |
0.64 |
0.60 |
120 |
1.19 |
1.14 |
1.10 |
1.06 |
1.0 |
0.92 |
0.82 |
0.75 |
0.69 |
0.63 |
0.59 |
150 |
1.19 |
1.14 |
1.10 |
1.06 |
1.0 |
0.92 |
0.82 |
0.75 |
0.69 |
0.63 |
0.59 |
185 |
1.19 |
1.14 |
1.10 |
1.06 |
1.0 |
0.92 |
0.82 |
0.74 |
0.69 |
0.63 |
0.59 |
240 |
1.20 |
1.15 |
1.10 |
1.07 |
1.0 |
0.92 |
0.81 |
0.74 |
0.69 |
0.63 |
0.59 |
300 |
1.20 |
1.15 |
1.10 |
1.07 |
1.0 |
0.92 |
0.81 |
0.74 |
0.69 |
0.63 |
0.59 |
400 |
1.20 |
1.15 |
1.10 |
1.07 |
1.0 |
0.92 |
0.81 |
0.74 |
0.69 |
0.63 |
0.59 |